What does voltage output mean for pressure sensor

The voltage output pressure sensor refers to the electrical signal that the sensor produces in response to the pressure it’s measuring. This output is usually a direct current (DC) voltage that varies within a specific range.

The voltage output is proportional to the pressure the sensor is measuring.

For instance,

In a 0-5V output sensor, if the sensor is designed to measure a pressure range of 0-100 psi (pounds per square inch), 0 psi would correspond to an output of 0V and 100 psi would correspond to an output of 5V.

A pressure of 50 psi would then correspond to an output of 2.5V.

Voltage Output Pressure Sensor

The relationship between the pressure and the voltage output is usually linear within the sensor’s specified range. This is often specified as a sensitivity in

  • millivolts per psi (mV/psi)
  • volts per bar (V/bar)

For example,

A sensor with a 0-5V output and a pressure range of 0-100 psi has a sensitivity of 5V/100 psi = 0.05 V/psi. This means that for every psi increase in pressure, the sensor’s output will increase by 0.05 volts.

The advantage of voltage output is that it can be easily interfaced with many types of electronics, including microcontrollers and data acquisition systems, which often accept voltage inputs.

However, voltage signals can be more susceptible to electrical noise and signal loss over long distances compared to current signals (such as 4-20mA), so they are often used in applications where the sensor is not too far from the control system.

How many voltage output types for pressure sensor

Pressure sensors can provide a variety of voltage output types, which are selected based on the specific needs and requirements of a given application.

1. Millivolt (mV) Output

These sensors usually provide a ratiometric output that is proportional to the power supply voltage.

For example, a typical mV output might be 1-100mV for a 1V power supply or 10-1000mV (1V) for a 10V power supply. These sensors are often used in low power applications or when the sensor is part of a Wheatstone bridge configuration.

For example, the low power applications are including:

  • Wearable Devices: Fitness trackers, Smartwatches, Heart rate monitors
  • Internet of Things (IoT) Devices : Environmental monitoring sensors, Smart home devices
  • Remote Sensing Stations: Weather stations, Seismic monitoring systems, Wildlife tracking systems
  • Medical Devices: Glucose meters, Portable ECG monitors, Oxygen saturation monitors
  • Wireless & Battery-Powered Systems: Motion detectors, Smoke detectors, Door/window sensors, Agricultural Sensors

2. 0.5-4.5V Output

These sensors usually provide a ratiometric output relative to the 5v regulated power supply voltage, where 0.5V represents the minimum pressure, and 4.5V represents the maximum pressure.

These are common in automotive and industrial applications due to their ease of integration with many microcontrollers.

0.5-4.5V Pressure Sensor regulated 5v supply

3. 0-5V Output

In these sensors, 0V typically represents the minimum pressure and 5V represents the maximum pressure. The 0-5V output is common and can be easily interfaced with a wide range of electronics.

In many cases, a 0.5-4.5V output pressure sensor can indeed replace a 0-5V output sensor, but you still need to consider a few points before decision make.

4. 0-10V Output

These sensors provide an output where 0V represents the minimum pressure and 10V represents the maximum pressure. They are often used in industrial applications where longer signal transmission distances are required.

5. 1-5V Output

1-5V and 1-6V are two types of voltage output ranges that can be used in pressure sensors. They are similar to the 0.5-4.5V output range in that they include an offset at zero pressure, but the specific values are different.

In a 1-5V output pressure sensor, the output voltage at zero pressure is typically 1V, not 0V. The maximum pressure that the sensor is designed to measure corresponds to an output of 5V.

Just like with a 0.5-4.5V sensor, a 1-5V sensor can provide a clear indication of a fault condition. An output below 1V or above 5V would indicate a problem with the sensor or the system.

6. 1-6V Output

A 1-6V output sensor works in a similar way, but the output at zero pressure is 1V, and the output at maximum pressure is 6V.

As with the other types of output, any voltage below 1V or above 6V would indicate a fault condition.

These types of output ranges are often used in industrial control systems where a clear indication of a fault condition is important. The specific output range used will depend on the requirements of the system and the electronics used to interpret the sensor’s output.

How to decide which voltage output is good for me?

When choosing the voltage output type for a pressure sensor, you’ll need to consider several important factors:

1. Power Supply

The availability and stability of your power supply are key considerations.

If your system primarily operates at 5V, a 0-5V or 0.5-4.5V output sensor might be suitable, if it is regulated 5V, 0.5-4.5v will be the best choice.

However, if you have a 10V supply, a sensor with 0-10V output might be more appropriate.

Pressure Sensor Output signal-2

2. Resolution

The output voltage range impacts the resolution of your measurements.

For example,

A sensor with a 0-10V output range offers twice the resolution of a sensor with a 0-5V range for the same pressure range. This is because the same change in pressure results in a larger voltage change for the 0-10V sensor.

If the pressure range remains the same, a 1-5V sensor would have lower resolution than a 0-5V sensor because the same pressure range is spread over a smaller voltage range.

Check the details of Resolution.

3. Fault Detection

Certain output types have built-in fault detection.

For instance, with a 0.5-4.5V sensor, an output below 0.5V or above 4.5V typically indicates a fault. This can be a useful feature if real-time monitoring of sensor health is critical.

Like the 0.5-4.5V case, 1-5V and 1-6V sensors can also provide fault indication by giving outputs outside of their normal range.

  • 5-4.5v
  • 1-5v
  • 1-6v

4. Compatibility

Ensure the sensor output type is compatible with the input specifications of your data acquisition system or control system. You wouldn’t want to choose a 0-10V sensor if your system can only accept 0-5V inputs.

Similarly, if your system has been designed to interpret 0V as the minimum pressure and 5V as the maximum, it might not interpret the 1-5V or 1-6V ranges correctly.

5. Noise Immunity

Environments with high electrical noise can interfere with voltage signals. In such scenarios, a current output such as 4-20mA might be more suitable due to its superior noise immunity.

Check the details of Noise and EMI

6. Transmission Distance

Voltage signals can degrade over long distances due to resistive losses in the transmission wires. If your sensor is far from your control system, a 4-20mA current output, which remains stable over long distances, might be preferable.

OutputTransfer DistancePower SupplyHighlight FeaturesMain LimitationsIndustries
mV output± 3m1.5mA | 5V1. Low power consumption
2. Ratiometric output
1. More susceptible to noise interference due to low voltage levels. 
2. Requires more care in system design to preserve signal integrity.
High precision industrial applications, Aerospace, Scientific Research
0.5-4.5V± 10m5V1. Good for fault detection
2. Lower power consumption
3. Widely compatible with devices
Lower voltage range, potentially resulting in lower resolution for the same pressure range.Automotive, Industrial Automation, HVAC
0-5V± 10m5V1. Full use of the 0-5V range for output
2. Good compatibility with many systems
No built-in fault detection like in the 0.5-4.5V or 1-5V sensors.Industrial Automation, Process Control, Automotive
1-5V± 10m5V1. Good for fault detection
2. Providing higher resolution than 0.5-4.5V
1. Slightly higher power consumption than 0.5-4.5V sensors. 
2. Compatibility may be an issue with some systems or devices.
Industrial Control Systems, Process Control, Aerospace
1-6V± 10m6V1. Good for fault detection
2. Providing even higher resolution than 1-5V
1. Highest power consumption among the three types. 
2. Compatibility may be an issue with some systems or devices.
Industrial Control Systems, Process Control, Aerospace
0-10V± 15m10V1. Full use of the 0-10V range for output,
2. Providing even higher resolution than 1-6V 
3. Compatible with systems that require 0-10V inputs
1. Requires higher power supply. 
2. No built-in fault detection.
Industrial Control Systems, Process Control, Aerospace
4-20mA>1000m24V | 36V1. High noise immunity due to current-based transmission.
2. Built-in fault detection (output < 4mA indicates a fault)
3. Transmit data over the same pair of wires 1000-m long
1. Requires a power supply that can provide sufficient voltage and current. 
2. A short circuit can potentially damage the power supply.
Industrial Control Systems, Process Control, Oil and Gas, Water Treatment

7. Power Consumption

Power consumption is more directly influenced by the design of the sensor’s internal electronics and the load that the sensor is driving. If the current drawn remains the same, a sensor with 0-10V output would not consume more power than a 0-5V sensor.

Smaller voltage ranges like 0.5-4.5V or 0-5V typically consume less power than larger ranges like 0-10V, which might be advantageous in power-sensitive applications.

8. Safety and Protection

Higher voltage levels may demand more careful handling and protection mechanisms.

A 0-10V sensor may require additional protection circuitry to prevent overvoltage conditions, which can add to the complexity and cost of the system.

Current and Voltage Output

How to balance between 0.5-4.5v and 0-5v?

The most important feature for 0.5-4.5V pressure sensor is that it can indicate faults by outputting a voltage less than 0.5V or greater than 4.5V.

This is a feature not available with a 0-5V sensor.

What is more, both sensors have a 4V-5V span, so they can provide similar resolution if they’re measuring the same pressure range.

So in many industry cases, a 0.5-4.5V output pressure sensor can indeed replace a 0-5V output sensor,

However, there are also cases when a 0.5-4.5V output cannot replace a 0-5V output,

For example:

1. Zero Pressure Reading:

If the system requires the sensor to output 0V for a zero-pressure reading and the device expects a 0V output to indicate zero pressure, a 0.5-4.5V sensor won’t be suitable because its minimum output is 0.5V.

2. System Compatibility:

If the system is designed and calibrated specifically for a 0-5V sensor, replacing it with a 0.5-4.5V sensor might require recalibration or adjustment of the system.

3. Maximum Pressure Reading:

If your system interprets 5V as the maximum pressure reading, a 0.5-4.5V sensor won’t be suitable because its maximum output is 4.5V.

It should be noted that you need to always ensure to check the system requirements and the sensor datasheet, or consult with a technical expert or the sensor manufacturer to ensure compatibility before replacing a sensor.

Industries for voltage output pressure sensor to use

1. Medical Devices

Medical devices such as blood pressure monitors, ventilators, and infusion pumps often use voltage output pressure sensors.

The need for high accuracy and resolution in these devices is paramount, as they directly influence patient health. Many medical devices are battery-powered, making the low power consumption of voltage output sensors an advantage.

For instance, a blood pressure monitor needs to detect very small changes in pressure to accurately measure systolic and diastolic blood pressure.

A voltage output pressure sensor with a high resolution can provide the precision necessary for such measurements.

2. HVAC Systems

In Heating, Ventilation, and Air Conditioning (HVAC) systems, pressure sensors are often used to monitor and control system performance.

Factors like air flow and filter status can be inferred based on pressure measurements. Since these systems are often digitally controlled, the easy interfacing of voltage output sensors to microcontrollers or other digital systems is a key advantage.

For example, a pressure sensor might be used to detect when a filter is becoming clogged (as indicated by an increase in differential pressure across the filter).

A voltage output sensor can provide a direct input to the system controller, enabling it to trigger a filter change alert.

3. Automotive Systems

Automotive systems use pressure sensors in a variety of applications, including tire pressure monitoring, fuel system control, and engine management. These systems often require sensors that can provide high-resolution measurements in a compact, low-power format, making voltage output pressure sensors an excellent choice.

In a tire pressure monitoring system, a small, low-power sensor is needed to fit within the wheel assembly and run on a small battery.

A voltage output sensor can meet these requirements, providing accurate pressure measurements to help ensure optimal tire pressure and vehicle safety.